Cages
Private Cabinets
Partial Cabinets
On-Net Products
. IP Transit
. Ethernet Transport Services
Standard Rack Configuration
. 48U Cabinets (Type: APC AR3107)
. Power extra (1) 110v/20 amp or (2) 110v/20A standard
Carrier Availability
. Cogent, Century Link
Facilities
. 480v 3-phase utility feeds - 8,000 amps (2 total feeds)
. 14,065 sq. feet of raised floor data center space
. Custom Cages available
. WIFI Available
Security
. C*CURE Card-Reader Access Control System
. (16) card readers total at all essential access points
. Entrance into a6ctual data center requires HID card swipe and unique pin code for access
. (9) IP cameras in use with recording and 24/7/365 monitoring capabilities to the Cogent NOC
UPS Systems
. (4) UPS Units - 750kVA each (Piller)
. "A+B" system - 2 UPS Units in parallel each
Battery Room
. (992) wet-cell UPS batteries (C&D)
. (248) batteries for each Piller UPS Unit
Generator Systems
. (3) Caterpillar Diesel Generators - 1,600kW each
. Generators work in parallel for redundancy
. All (3) units share (2) 6,000 gallon diesel fuel tanks
Electrical
. (22) Liebert PDUs in data center - 225kVA each
Fire Systems
. Fire suppression and detection system consists of heat detectors, smoke heads, preaction sprinkler system, and separate Inergen gas-tank system
. (242) Inergen tanks
. Vesda air sampling smoke detection system
HVAC
. Chilled Water system (2) Trane chillers
. Chillers work in "redundant" setup
. (12) 50-ton chilled water CRAC units in Data Center (Manufacturer: Data Aire)
. (2) 13,000-gallon backup water storage tanks