Cogent Herndon is located in the area Reston, USA (America), and the colocation data center is carrier neutral. The data center was last updated on 26-12-2018.
Facilities - 12,900 square feet of raised floor colocation space - Manned 24x7 840 square foot NOC
Security - C*CURE Card-Reader Access Control System - (14) card readers located at essential access points entrance into data centers require HID card swipe and unique pin code for access - (18) cameras tied into software with recording and 24/7 monitoring capabilities
HVAC - 28 CRAC units, 10 ATS, and 18 Airflow with rooftop mounted condensers - Separate remote mounted humidifiers for HCs. - 1 Carrier rooftop unit for Battery room
UPS Systems - 3 UPS Modules @ 375 KVA each (MGE EPS 6000) working in parallel - 1 MGE Static Transfer Switch
Battery Room - 3 Strings (total number of batteries: 240) - C&D Dynasty Model UPS12-400MR Sealed
Electrical/Fire/Monitoring - United Power PDUs (8) and EDMs (8) - 480v 3-phase utility feed - 3,000 amps - Fire Detection and Suppression consists of above and below floor smoke heads, FM200 - tanks, and a pre-action sprinkler system in hosting centers.
Generator Systems - Spectrum Diesel Generator, 1500kw/1875kVA - 5,000 gallon diesel storage tank - Auto Transfer Switch - "Tap Box" connection in place for portable generator emergency usage