Cogent New York is located in the area New York, USA (America), and the colocation data center is carrier neutral. The data center was last updated on 26-12-2018.
On-Net Products - IP Transit - Ethernet Transport Services
Standard Rack Configuration - 42U Cabinets (Type: APC AR3100) - Power extra (1) 110v/20 amp or (2) 110v/20A is standard
Carrier Availability - In Data Center - Verizon & Charter
Facilities - 480v 3-phase utility feed - 3,000 amps - 480v 3-phase utility feed - 2,500 amps - 24,608 square feet of non-raised floor data center space
Security - C*CURE Software House Card Reader Access Control System (11) card readers total at every essential door - Entrances into actual data center areas requires HID card swipe and unique pin code for access - (13) cameras tied into software with recording and 24/7 monitoring capabilities - 24/7/365 Building Security need to sign in and show proper ID for access to the 6th floor.
UPS Systems - (4) UPS Units - 400kVA each (Pillar UB R 400) - A&B System - 2 UPS Units in "parallel" each - Each UPS has (3) strings of batteries - 120 total
Generator Systems - Caterpillar Diesel Generator - 1,500kW unit (Model 3512) - 6,000 gallon diesel fuel storage tank - Fuel Pump Transfer System - "Tap Box" Connection in place for emergency portable generator use
Electrical - ASCO Automatic Transfer Switch - 1,000 amps - RussElectric Automatic Transfer Switch - 2,500 amps - (4) United Power PDUs
Fire Systems: - Pre-action & dry pipe sprinkler fire suppression systems
HVAC - (15) 20-ton Liebert HVAC units with rooftop dry coolers for the data center and electrical area - (2) 10-ton Stulz HVAC units with rooftop dry coolers for the data center