Data Center Map

Element Critical Chicago Two

Element Critical
341 Haynes Dr
60191 Wood Dale
Illinois, USA
Visit Website

Cages
Footprints
Private Cabinets
Partial Cabinets
Individual Servers
Remote Hands
Bare Metal Servers
Public Cloud Servers


N/ABuilding Features
44,520 sq. ft. facility size
26,000 sq. ft. raised floor
Full interior loading dock
Annual ISO and SSAE16 audits
Ladder rack system
18-inch deep, bolt down stringer system
Cabinets grounded independent of raised floor system
9 feet 6 inches ceiling height
Loading capacity: 625 pounds per sq. ft.


Environmental Controls
Split System - DX (Direct Exchange) system
(24) 30-ton Liebert air conditioning (CRAC) units, 720 tons cooling capacity
VESDA (Very Early Smoke Detection Apparatus)
Intelligent addressable detectors and initiating devices
DataTrax monitoring system monitors all CRAC units, electrical and mechanical infrastructure, utility power, ATS, UPS, and PDUs for various alarm conditions, temperature, humidity and other potential alarm conditions
Pre-action sprinkler system

Connectivity
Meshed, multi-vendor internet transit connectivity
Multiple ILEC and CLEC access providers
Diverse path long haul access (public and private)
Diverse fiber entry and intra-building fiber paths
Redundant internal network distribution platforms
Dual customer physical handoffs (copper, single-mode and multi-mode fiber)
Private production and recovery MPLS backbone access dedicated to Sungard AS subscriber traffic
Recovery-centric on-demand network service suite supporting a broad range of TDM and IP services
Integrated monitoring and management systems for comprehensive fault identification and remediation

Power Management
(2) diverse 12 kV ComEd electrical feeds
(2) ComEd service transformers
(2) redundant automatic throw over switches
(6) Liebert 675 kW modules
2,025 kW total capacity
A/B power source capability
(6) strings of wet cell UPS batteries, 60 batteries in each string
(22) Liebert Power Distribution Units
(2) Cummins diesel generators (1,750 kW and 1,500 kW), redundant fuel pumps, 8,000 gallon diesel storage tank

Element Critical Chicago Two Brochure.pdf
Element Critical - Chicago Data Center Campus
Element Critical Chicago Two Pricing
If you are looking for colocation, cloud, connectivity or other services in Element Critical Chicago Two, or other data centers in Chicago or by Element Critical, please try our free quote service or reach out for a free consultation about your data center needs.
Advertisement
Nearest Data Centers
DistanceData CenterAddress
0.18 milesElement Critical Chicago One711 N. Edgewood Ave.
1.37 milesCentersquare - Chicago ORD22425 Busse Road
1.39 miles1400 East Devon Avenue (CH3)1400 East Devon Avenue
1.45 milesStream DC Chicago II1925 Busse Road
1.46 milesSkybox Chicago I800 E Devon Ave
1.47 miles2200 Busse Road (CH1)2200 Busse Road
1.47 milesRackspace Chicago2200 Busse Road
1.51 miles2299 Busse Road (CH2)2299 Busse Road
2.02 milesEquinix CH31905 Lunt Avenue
2.07 milesEdgeConneX Chicago - EDCCHI011800 Nicholas Blvd

Element Critical
Data Center Operator at
Element Critical Chicago Two
341 Haynes Dr
Site Code: CH2
Headquartered in San Francisco, California

5