Standard Rack Configuration
- 42U (APC Cabinets Model AR3100)
- Power extra (110v/20amp or 2x 110v/20amp is standard)
Carrier Availability
- AT&T
Facilities
- 9,151 sq feet of non-raised & raised floor colocation space
- Custom cages available
- 480v 3-phase utility feed - 2,800 amps
Security
- Building system access badge required for after-hours, weekends, and holidays
- C*CURE Card-Reader Access Control System
- Entrance into data center rooms require HID card swipe and unique pin code for access
- Data Center Room #5: Mantrap cage w/ pin code entry for additional security (required before entering room)
- (5) IP cameras with recording and 24/7 monitoring capabilities to the Cogent NOC, including (1) at each main entrance for Suites #5, 203, and 214
HVAC
- 2 Liebert 40-ton chilled water HVAC units in Room #5.
- 2 Liebert 50-ton chilled water HVAC units in Room #5.
- 2 Airflow 8-ton units & (1) 18-ton unit in Room #203 (Rooftop Mounted Condensers)
UPS Systems
- 2 UPS units for potential "A & B" feeds
- UPS Unit Models: PowerWare 9390 and APC Galaxy 5000
- 1 Battery Cabinet for each UPS unit - 1 string of 40 batteries each UPS Unit; 80 Batteries total
DC Power
- 4 Rectifiers - Mfg. TDI
- 4 strings of DC Batteries - 16 total
Generator Systems
- 1 900kW Katolight Diesel with 600 gallon tank
- 1 500kW Katolight Diesel with 600 gallon tank
Electrical/Fire/Monitoring
- Fire suppression & detection system consists of smoke detectors, heat sensors and FM200 tanks
Cogent Oakland Pricing
If you are looking for colocation, cloud, connectivity or other services in Cogent Oakland, or other data centers in Oakland or by Cogent Communications, Inc., please try our
free quote service or reach out for a
free consultation about your data center needs.