Facts:
- Total Square Feet: 700,000 sq ft
- Total Square Feet of Raised White Floor: 400,000 sq ft
- Fire detection – VESDA for DH.
- Fire suppression – Pre-Action, NFPA 13 Compliant for DH. Wet system for Offices.
- Construction type – II-B
- Building type – Data Center (Precast Structure/Façade)
Floor load capacity
- 1st floor DH – 250 psf dead load, 2000 lbs concentrated load
- 2nd Floor DH – 250 psf dead load, 100 psf hanging load below the floor
Power
- Utility capacity – 135 MW total
- Utility voltage – 34.5 kV
- Number of Utility Feeders – 4 (2 redundant)
- Number of transformers on site – 40 each
- UPS configuration and capacity – 4:3 distributed redundant, 1500 kW each
- Generator power – 2250 kW x 80 each = 180 MW
Cooling
- York Roof Mounted Air Cooled Chillers
- 530 tons x 70 each = 37,100 total tons of DH cooling
Security:
- Security Fencing, Entrance Gates
- Full-time guards on Site