AdNet - DataCity Bucharest is located in the area Bucharest, Romania, and the colocation data center is carrier neutral. The data center was last updated on 04-07-2017.
TIER III DESIGN: Availability higher than 99.982% Redundant power elements with independent circuits paths configured in as 1+1 Redundant cooling elements with independent circuits paths configured in as N+1 Provides concurrent maintenance
ENERGY EFFICIENT: Optimized IT Equipment arrangement in Cold/Hot Aisle Advanced multistep cooling control allow for high efficiency Integration of green energy such as photovoltaic and wind turbine High performance rectifiers, inverters and accumulators in UPS system Targeted PUE - Power usage effectiveness lower than 1.3 for 100% load Actual PUE - 1.75 at 20% Load
IT & TELECOM INFRASTRUCTURE: IT infrastructure design for TIER III Multipath optical fiber on 3 circuits High end border routing equipment Juniper MX series Data Center L2 and L3 switching performed by Cisco Nexus Complex evolved virtualization platform based on Cisco UCS, HP 3PAR storage and VMWare VCenter/Vsphere Cluster balancing technology from A10 Networks Advanced traffic anomaly detection and cleaning with Arbor System technology Complete internal data circuits distribution with Panduit materials
COOLING: Adiabatic & Free cooling - Indoor for IT Containers: 60 racks with average power of 7 KW arranged in 3 cold aisle with 20 racks each resulting in a total power of 140KW / cold aisle 24 LCU providing 20KW of cooling arranged in 3 cold aisle resulting in 8 units / row with a capacity of cooling of 160KW (7+1) In-line positioning with racks, Cold-Isle/Hot Isle containment with front to back airflow Cooling agent: thermic agent with heat transfer properties optimized for whole range of meteorological conditions Chiller water cooling - Outdoor: 3 x 300KW chiller units with Free Cooling mechanism "Air-Conditioning" type water cooling - compressors based in 12 steps (4 independent compressors / chiller unit) N+1 Redundant compressors, ventilators and other components (according to TIER III standards for cooling) Automation system for adjusting electrical energy consumption Adiabatic & Free cooling - Indoor for Power containers 4 units 30KW N+1 redundancy type according to TIER III standards for power supply
POWER & UPS: Total installed power 480 kW x 2 with redundancy in 2 lines 2 automatic back-up diesel generators one for each line Accumulators pack - 108 with 100 Ah capacity for each power box 2 UPS of 40 kVA for chiller pumps 2 UPS of 20 kVA for interior modules of inline cooling units 2 heating pumps and 1 ice pillar for extra heat removal before Chillers 1 wind turbine with 2 KW - providing auxiliary power 80 x 250W (20 KW) photovoltaic farm - compensating in extra hot summer days
RACKING & VIRTUALIZATION: Racks Hardened steel Racks: 45U racks space proving at least 42U usable IT Equipment Depth: 1000mm Width: standard 19'' PDU: for each Rack 2 PDU three-phase power supply of 400V - Maximum power 11 KW redundant/ Rack, each PDU with 24 IEC13 sockets and 6 IEC19 sockets Assembling on metallic anti vibration and anti seismic system
Virtualization system Cisco UCS Blade Server System 5 x Blade server chassis each with 8 blade server units installed Installed processing power ~ 1800 VCPU Installed memory : 7168 GB HP 3PAR 7400 Enterprise Storage Dual controller with 200TB of usable space (250TB installed) Storage: even mix of SAS/NL-SAS disk Switching: Integrated Cisco switch fabric with extra 32 port 10GB for external connectivity VMWare VSphere/VCenter Enterprise plus virtualization system
SECURITY SYSTEM: Complex security system Fire detection system Smoke detection sensor Temperature sensor Fire extinguisher cylinders Fire detection station Exterior fire alarm control panel from fast access from outside Dual power source, both from main power supply and UPS Access control module Emergency fire path - both mechanical and electromagnetic Magnetic stripe card access Unlimited user access with multiple roles and rights Control panel integration with fire detection and extinguisher system - automatic fire path unlocking Real time reports and history : access type, users, access path, etc. Surveillance system HD IP cameras NVR recording and monitoring Minimum 30 days data storage in
INFRASTRUCTURE MANAGEMENT: Complex monitoring and management software suite integrating all hardware and software components installed in the datacenter infrastructure (power elements, cooling elements, security & surveillance, sensors & monitoring devices) Data center components detailed charts and schematics (racks, cooling, power, surveillance, control access, sensors, etc.) IT Equipment layout Power supply, circuits and distribution Chillers, LCU, cooling paths Surveillance, access control, firefighting systems Humidity, temperature, air quality, flood sensor system Renewable energy controllers Real time & Historical monitoring for all managed systems Statistics, Graphics and Analysis of various parameters Friendly graphical web user interface compatible with most modern browsers
CONNECTIVITY: Physical connections (L1): 3 paths geographically and logically independent underground optical fiber links - 144 optical wires available Open Third-party fiber optic interconnection cabinet easily accessible from any underground infrastructure Logical connections (L2-L3): Data center node is included in main N x 10Gbps metropolitan multi-ring core network of 2K Telecom, providing high capacity resilient communications with most POP or exchange nodes Juniper MPLS Switches and Routers provide any type of logical connection (L2 circuits, VPLS, L3 VPN, QinQ, Dark Fiber, TDM transport, etc.) External connections (National&Internet) 2KTelecom is member of public Internet Exchanges: Interlan, Balkan-IX RoNIX, NxData, IBM Data Center, INES Datacenter, Cyberhost Datacenter Extra private national interconnection with leading ISP providers improve capacity and latency Optimized Balanced Access to Internet is achieved through major world wide Internet Carriers (M247/NTT, Telekom/LEVEL3)