On-Net Products
- IP Transit
- Ethernet Transport Services
Standard Rack Configuration
- Height: 42 U, Size: 600 x 1000 mm
- Power: 1x16 amp circuit (AC/230V) OR 1x32 Amp circuit (DC/48V)
Carrier Availability
- Cogent
- Orange
Facilities
- 250 m² (2,345 sqft) of raised floor colocation space
- 24x7 access control (card access + NOC intercom)
- Main entrance and colo room camera in use with recording and 24/7/365 monitoring capabilities to the Cogent NOC
HVAC
- HIROSS HVAC units, 4 x 40 kW
Generator Systems
- AUSONIA Diesel Generator, 200 KW
- 2000 liters diesel tank
- Automatic Transfer Switch.
UPS Systems
- AC/230V: 2 x BENNING UPS modules @ 20 kVA each
- DC/48V: 6 x BENNING DC modules @ 10.8 kVA each
Battery Room
- DC/48V: 2 string of batteries
Electrical/Fire/Monitoring
- Fire Detection and Suppression consists of above and below floor smoke heads, FM 200 tanks, Siemens/Cerberus Early Warning and Detection System, and a preaction dry system