Standard Rack Configuration
. 42U APC Cabinets (Model: AR3100).
. Power extra (110v/20 amp or 2x 110v/20amp is standard)
Facilities
. 11,521 square feet of raised floor data center space
. 480v 3-phase utility feed - 1600 amps
. Custom cages available
Security
. C*CURE Card-Reader Access Control System
. 13 card readers total at all essential doors
. Entrance into actual data center requires HID card swipe and unique pin code for access
. Four IP cameras in use w/ recording & 24/7 monitoring capabilities to the Cogent NOC, one at main entrance into data center
. 24/7 building security w/ video camera surveillance
. Building system access badge required after hours, during weekends and on holidays
UPS Systems
. 225kVA UPS Unit (Model: Powerware 9315)
. 40-battery string for UPS Unit (C&D)
Generator Systems
. Caterpillar Diesel Generator, 1500kW
. 4,000 gallon diesel tank
. 2,000 Amp RussElectric Automatic Transfer Switch
HVAC
. (5) 20-ton Airflow HVAC units with rooftop condensers provide cooling for data center floor.
. (3) 5-ton Airflow HVAC units with rooftop condensers provide cooling for electrical/power rooms
Electrical/Fire/Monitoring
. Fire suppression & detection system consists of heat detectors, smoke heads and a pre-action sprinkler system