On-Net Products
- IP Transit
- Ethernet Transport Services
- Utility Computing
Standard Rack Configuration
- Height: 42 U, Size: 600 x 1000 mm
- 1x6amp, 1x10amp, 1x16amp, circuit (AC/230V) OR 1x32 Amp circuit (DC/48V)
Carrier Availability
- SFR, Colt, Orange, & Verizon
Facilities
- 600 m² (5,630 sqft) raised floor colocation space
Security
- 24x7 access control (card access + NOC intercom)
- Main entrance and colo room camera in use with recording and 24/7/365 monitoring capabilities to the Cogent NOC
HVAC
- HIROSS HVAC units, 4 x 40 kW.
Generator Systems
- SDMO Diesel Generator, 370 kW
- 3000 liters diesel tank
- Automatic Transfer Switch
UPS Systems
- AC/230V: 2 x BENNING UPS modules @ 40 kVA each
- AC/230V:5 x BENNING UPS modules @ 20 kVA each
- DC/48V: 6 x BENNING DC modules @ 10.8 kVA each
Battery Room
- DC/48V: 2 string of batteries
- Designed for 12 hr. back-up
Electrical/Fire/Monitoring
- Fire Detection and Suppression consists of above and below floor smoke heads, FM 200 tanks, Siemens/Cerberus Early Warning and Detection System, and a preaction dry system.