On-Net Products
- IP Transit
- Ethernet Point-to-Point
Standard Rack Configuration
- 42U Cabinets (Type: APC AR3100)
- Power extra (1) 110v/20 amp or (2) 110v/20A is standard
Carrier Availability -In Data Center
- Bell Canada, Cogeco, Rogers, & AllStream
Facilities
- (2) 600v 3-Phase utility feeds - 2,500 amps
- WIFI available
HVAC
- (10) 20-ton Liebert HVAC units with rooftop condenser units provide cooling for data center floor
- (2) 12-ton Carrier HVAC Units in UPS room
Fire Systems
- Fire Suppression System consists of under raised floor Co2 system smoke detectors below raised floor, on, and above ceiling
UPS Systems
- (3) UPS Units providing "A&B Power"
- (1) Mitsubishi UPS Unit -300kVA (9800A Series)
- Mitsubishi UPS unit has wet-cell battery plant -45 batteries total (comprises one string)
- (1) Schneider Electric UPS Unit -160kVA (Galaxy VM Series)
- (1) Modular Battery Cabinet
- (1) Schneider Electric UPS Unit -225kVA (Galaxy VM Series)
- (1) Modular Battery Cabinet
Generator Systems
- (3) Caterpillar Diesel Generators "A+B" for UPS Units
- (2) 800kW Generators
- (1) 574 kW Generator
- (2) diesel "day tanks" feed back to the main building diesel storage fuel tank, which is 5,000 gallons
- (12) ASCO Automatic Transfer Switches
Security
- Card Reader Access System (CCURE Software House) -(8) card readers total entrance into actual data center requires HID card swipe and unique pin code for access
- (8) cameras installed with local DVR unit -remote monitoring and recording capabilities (4) IP cameras tied into separate software with recording and 24/7 monitoring capabilities
- 24/7 lobby security (customers need to be on access list to get to 3rdfloor after hours, weekends, and holidays)